Abstract

This paper analyses the formation mechanism of the transmission distortion of electronic voltage transformer, and points out that the integrator will magnify the transient transfer error and superimpose the dynamic additional component on the output signal, which may cause the transfer distortion of voltage signal in serious cases. To restrict the electronic transformer transient variable error effect on distance relay, a distance relay method using instantaneous value after equal transfer processes is proposed. It directly uses output differential signals of the capacitor voltage divider and Rogowski coil. The capacitor voltage divider and Rogowski coil are decomposed into several typical variable link in series. The virtual digital transfer link, which is constructed by the digital filter, is used to compensate for the difference parts of the transfer link, so that the voltage and current signals pass through the same transfer link. It can mitigate the influence of voltage and current signal transfer difference on the calculation accuracy of distance relay. The simulation results show that the proposed distance relay method has fast operation speed and is less affected by abnormal voltage and current signal transfer, and its performance is better than existing distance relay methods.