Abstract
An improved differential equation method for earth fault location in non-effectively earthed system is proposed. Karrenbauer transformation is used to construct the compound mode network of single phase earth fault. Based on the mode network, the fault equation including mode voltage, mode current, line parameters and earthed resistance is derived .The fault distance can be gotten by solving the equation with the least square estimation. In the calculation characteristics of different line models are compared and model is proved to be the best in accuracy and simplicity. ATP simulation and laboratory test proved that the proposed fault location method is feasible and has satisfactory accuracy. Because of using transient signal, the method is more sensitive and only need half cycle data, which can accelerate fault location speed and be more applicable. (6 pages)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.