Abstract

AbstractThis paper is concerned with the transformer coil dc leakage current under different conditions. These conditions include in‐air, and in‐oil leakage, currents with or without artificial coil deposits. In‐oil leakage, currents are investigated when the coil is immersed in new or used transformer oil at different temperatures. The results showed that the leakage current increases with the increase in the applied voltage and oil temperatures. The rate of increase in leakage current with temperature depends on the transformer oil and coil conditions. The in‐oil leakage currents are higher than those obtained in air. The leakage currents measured in used oil are higher than those resulted in new oil. Copper deposits cause higher values of leakage current than iron deposits for the same medium, applied voltage and temperature. Deposits increase the leakage current for different coil surrounding media. A linear model for the leakage current as a function of the applied voltage under different conditions has been found and its validity has been justified by statistical consideration. The parameters of this model account for various experimental conditions. Copyright © 2006 John Wiley & Sons, Ltd.