Abstract
For an air source heat pump (ASHP) unit with a vertically installed multi-circuit outdoor coil, it is rarely possible to make the frost accumulations on each circuit's surface equal, leading to different frosting evenness values (FEVs) as a reverse cycle defrosting operation starts. On the other hand, uneven defrosting phenomenon was found and reported as many methods were developed to improve defrosting performance of ASHP systems, which may be attributable to the reverse cycle defrosting starting at an uneven frosting. Understanding of defrosting performance of an ASHP unit with a multi-circuit outdoor coil at different FEVs is of importance for ASHP units' application, but studies are scarce in the open literatures. In this paper, we report an experimental study on defrosting performance when frost accumulated on the surface of outdoor coil at different FEVs. This paper presents details of an experimental ASHP unit and the experimental conditions, followed by results, and conclusions. Finally, an increase of 6.8% in defrosting efficiency was confirmed when the FEV changed from 82.6% to 96.6%.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.