Abstract
In hot and humid regions, the non-ignorable thermal resistance of condensate film can weaken the process of heat and mass transfer under total condensation in the dry channels of indirect evaporative cooler (IEC). In this study, the average thickness of condensate film was proposed and a comparison of thermal resistance of plate and condensate film was investigated under total condensation by a visualized cross-flow indirect evaporative cooler (IEC) experiment system. The experimental results showed that condensate film could be formed and the thermal resistance of condensate film was non-ignorable under total condensation due to thick water film. It could be a guidance in terms of reducing thermal resistance, saving energy and proposing a novel mathematical model under total condensation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.