Abstract

The ac arc propagation over a wet contaminated surface is observed using high speed cameras located at two sides. It is found that the reignition processes at different parts of the arc are different. Based on the observation and analysis of the movement of the arc roots, it is demonstrated that the electric breakdown process plays a significant role in the propagation of the arc. A new propagation mechanism based on electric breakdown developing ahead of the arc column is proposed to describe the physical process of the movement of the arc root. Comparison of the proposed mechanism with arc propagation phenomena in previous literatures shows that the proposed model is reasonable.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.