Abstract
In this study, the heat transfer and friction characteristics of the 5.3 mm O.D. slit-finned heat exchangers under wet condition have been experimentally investigated. Plain-finned heat exchangers having the same 5.3 mm O.D. tubes are also tested for comparison purpose. The effect of fin pitch on j and f factor is negligible. Slit fin samples yield higher j and f factors than plain fin samples. For one row configuration, the average f factor ratio between slit fin sample and plain fin sample is 2.18. The ratio increases to 2.41 for two row configuration, and to 2.65 for three row configuration. As for the j factor, the ratios are approximately the same (1.61, 1.70 and 1.71 for one, two and three row configuration). Both j and f factor increase as the number of tube row decreases. The same trend is observed for the plain fin samples. At high Reynolds numbers, the j/f ratios of the slit fin are approximately the same as those of the plain fin. At low Reynolds numbers, the j/f ratios of the slit fin are smaller than those of plain fin. Data are compared with existing correlations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.