Abstract

The jet-pump refrigerator cycle offers a low-capital-cost solution for utilizing low-grade waste heat in the production of cooling for buildings and process refrigeration. The heart of the jet-pump refrigerator is an ejector, the performance of which strongly determines the thermal efficiency of the cycle. This paper describes and evaluates the results of an experimental investigation into the operation of ejectors primarily for use in jet-pump refrigerators. The construction of a steam-steam ejector test facility and experimental method are described. Experimental results are provided concerning the effects of primary nozzle exit position within the mixing-entrainment section, primary nozzle exit and diffuser throat areas. The causes and effects of flow instability under conditions of high secondary pressure ratio are also discussed and methods of increasing the critical condenser pressure are identified and rated in order of effect.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.