Abstract

The thermal performances of a minichannel heat sink are experimentally investigated for cooling of electronics using nanofluid coolant instead of pure water. The Al2O3–H2O nanofluid including the volume fraction ranging from 0.10 to 0.25vol.% was used as a coolant. The effects of different flow rates of the coolant on the overall thermal performances are also investigated. The flow rate was ranged from 0.50 to 1.25L/min as well as the Reynolds number from 395 to 989. The coolant was passed through a custom made copper minichannel heat sink consisting of the channel height of 0.8mm and the channel width of 0.5mm. The experimental results showed the higher improvement of the thermal performances using nanofluid instead of pure distilled water. The heat transfer coefficient was found to be enhanced up to 18% successfully. The nanofluid significantly lowered the heat sink base temperature (about 2.7°C) while it also showed 15.72% less thermal resistance at 0.25vol.% and higher Reynolds number compared to the distilled water.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.