The present study reports the results of an investigation of an ejector refrigeration system working with refrigerant R-134a, aiming at the enhancement of the pressure recovery. The critical condition has been determined for three mixing chambers of equal internal diameter but different profiles and for several stagnation conditions of primary and secondary fluid. The influence of both the nozzle longitudinal position and the vapor superheating of the primary and secondary fluid stagnation states on the mass ratio has also been reported. Experimental results have shown a negligible performance increment of the new mixing chamber designs, “B” and “C”, with respect to a standard design one, “A”, with the mixing chamber “C” underperforming the other two over all the performed tests. A new performance parameter has been introduced being defined as the ratio between experimental and a 2nd law based theoretical mass ratio.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.