Abstract

Laboratory simulation of aeolian vibrations was used in determining the fatigue characteristics of an ACSR conductor subjected to constant and varied amplitude loadings. Using linear regression analyses, S-N curves for first-through fifth-strand breaks were fit to the data, and a pseudoendurance limit of 21.31 MPa (3.09 ksi), was estimated. Subjecting the conductor to three different types of load sequences revealed that M.A. Miner's cumulative damage hypothesis (1945) is somewhat conservative, but can be assumed valid for design purposes. This information, in conjunction with the actual load histories, will allow electric utility companies to design transmission lines more accurately. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.