Abstract

Direct and indirect evaporative cooling system is experimentally investigated using a plate heat exchanger for hot climate conditions. The effects of chilled water and ambient temperatures, water flow rates, humidity, and the operating cooling mode on the supply air temperature was investigated for three configurations. The system dry bulb and wet effectiveness was estimated for all conditions under consideration. It was found that the dry bulb effectiveness approached 17%, while it was in the range of 72-98% for the wet bulb effectiveness. In addition, the secondary air saturation effectiveness was calculated with varying water flow rates. It was found that the increase of water quantity in the heat exchanger would increase the refrigeration capacity and lead to a higher secondary air temperature difference. This resulted in higher saturation effectiveness for the system. These results were compared with available numerical data for calibration and validation purposes.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.