Abstract

Electric Arc Furnaces (EAF) are nonlinear loads causing power quality problems on the systems they are connected to. The main reason of EAFs causing power quality problems is the nonlinear characteristics of the electric arc. In this study, dynamic working characteristics of electric arc furnace load at Sivas Iron and Steel Incorporated Company (SIDEMIR) operating with 60 MVA EAF have been experimentally examined by HIOKI 3197 PQ analyser. Utilizing the measured dynamic load curves, mathematical equation and proper parameters have been determined for modelling electrical arc with the help of curve fitting methods on Matlab program. Also by modeling a phase equivalent of the system and harmonic filters existing on the system, a time domain model has been formed and with this model, harmonic effects of the EAF have been examined with Matlab/Simulink. Simulation results show that the presented model can be used for examining PQ and voltage harmonics problems caused by EAF loads.DOI: http://dx.doi.org/10.5755/j01.eie.23.3.18328

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.