Abstract

In this paper, a finned tube condenser performance test platform by using hot water as heat transfer medium in the pipe was established. The air side correlations of pressure drop and heat transfer were acquired based on lots of testing datas.A segment by segment model of the finned tube condenser used in these correlations was proposed and a simulation program was developed by using Visual C++ programming tools. Experiment and simulation results show that the air side correlations of pressure drop and heat transfer are fitting well with experimental datas. The deviation between the experimental and calculated values is within ±5%.The deviation of Nu Number is within ±10% and the deviation of the pressure loss is within±15%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.