Abstract

High-voltage direct current system using modular multilevel converter (MMC-HVDC) is a potential candidate for grid integration of renewable energy over long distances. The dc-link fault is an issue MMC-HVDC must deal with. This paper proposed an enhanced MMC topology with dc fault ride-through capability. By using diode clamp sub-modules, the freewheeling effect of diodes is eliminated and fault currents can be very rapidly extinguished. Since the tripping of circuit breakers is avoided, MMC can immediately restart power transmission for non-permanent faults. The required rated voltage of additional semiconductors is half the conventional semiconductors, resulting in low extra cost. Simulation results using PSCAD/EMTDC have verified the validity of the proposed protection scheme.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.