Abstract

The model, referred to as FLASH-CAT (Flame Spread over Horizontal Cable Trays), was developed to estimate the heat release rate for vertical cable tray fire. The focus of this work is to investigate the application of an enhanced model to the single vertical cable tray fires with different cable spacing. The experiments on vertical cable tray fires with three typical cable spacing were conducted. The histories of mass loss rate and flame length were recorded during the cable fire. From the experimental results, it is found that the space between cable lines intensifies the cable combustion and accelerates the flame spread. The predictions by the enhanced model show good agreements with the experimental data. At the same time, it is shown that the enhanced model is capable of predicting the different behaviors of cable fires with different cable spacing by adjusting the flame spread speed only.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.