The unbalanced and distorted grid voltage is a common fault in practical power system. The effects of unbalanced and distorted grid voltage on the current control of three-phase ZVR grid-connected inverter are analyzed in detail. To solve the problem of distorted output currents, an enhanced control strategy based on PI + multi-resonant controller is proposed, and controller parameters are designed by the system model. This control strategy does not need the extraction of positive-sequence and negative-sequence component, and it is convenient to realize. The simulation model and experimental platform are constructed, and simulation and experimental studies have been carried out. The obtained results validate the correctness of the theoretical analyses and the effectiveness of the proposed control strategy. It is demonstrated that the proposed control strategy can reduce the output current THD under unbalanced and distorted grid voltage conditions, and the current quality is significantly improved.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.