Abstract

In allusion to the reverse power detection of grid-connected irreversible-flow PV generation system, a reverse power detection method based on fitting algorithm of the ellipse parameters and delayed signal cancellation(DSC) is proposed. According to the different features of coefficient of elliptic equations under the occurrence of reverse power and grid fault, whether the reverse power or the fault was occurred can be rapidly detected and judged. The time-domain based DSC algorithm is adopted to eliminate the influence of power grid harmonics on the detection accuracy and real-time performance of the proposed algorithm. Results of both MATLAB/Simulink based simulation and actual operation show that the least square for fitting ellipses method and the proposed cascaded DSC algorithm can accurately distinguish reverse power from power grid fault around a cycle after the occurrence of the reverse power, and the proposed method possesses strong robustness for noise, and the proposed method is feasible.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.