Abstract

Grid integration of distributed energy resources has become a technical challenge in the distribution network operation due to the intermittent nature of renewable energy sources and their impact on grid voltage stability. Thus, a dynamic voltage restorer (DVR) is installed in the distribution network system to reduce such grid voltage impact on sensitive loads. In this article, a pseudo-derivative-feedback (PDF)-based voltage controller is implemented for the effective operation of DVR under voltage disturbances. Response of DVR primarily depends upon its controller action. This article addresses the issues in conventional P and PI multiloop controller with and without feedforward path then proposes PDF control strategy for DVR. Using the proposed controller, dynamic performance of DVR is improved. The efficacy of the proposed controller is illustrated by a comparative study with conventional P and PI controller using time response and relative stability analysis. Finally, PSCAD simulation studies for a 10 kV medium voltage DVR and experimental results using a low voltage laboratory prototype DVR are presented to prove the robustness of proposed controller for DVR under symmetric and asymmetric voltage sags.