Abstract
A novel method of identifying the coherency of a group of generators is presented. The method requires values of generator rotor angles at three distinct instants of time in the early part of the transients. Also, a measure of the degree of electrical coupling between the generators is required. The angles are calculated during the faulted and part of the postfault period through Taylor-series expansions. The degree of coupling is calculated from an admittance distance measure. The proposed method has been tested on five different power systems of varying sizes. It is concluded that the results obtained by the proposed method match perfectly those obtained through simulation of the total system dynamics.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.