Abstract

An analytn model for working fluids flowing through capillary tubes has been established with the approximate integral method. All the possible flow regimes in the capillary tubes, including subcooled, two-phase and superheated regimes, are covered in the model, and different analytic solutions are given respectively for each flow regime. As examples, the mass flow rates of refrigerants R12, R134a and R600a through capillary tubes are predicted by the model, and compared with those evaluated by a general distributed-parameter model. The mean bias falls into 1% and the maximum bias is 2.2%, while the computation speed of the new model is more than one order of magnitude higher than that of the distributed-parameter one.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.