Abstract

This paper presents an algorithm that improves steady state security of a power system. An objective function which includes power flows in the overloaded system elements and bus voltages that exceed the permissible limits is formulated. Weighting factors, obtained from the magnitudes and frequencies of the violations, are also used in this function. An optimal combination of controlling variables, such as voltage magnitudes at generator buses, real power generation, transformer and phase shifter tap settings, is determined by minimizing the objective function. Instead of the non-linear load flow equations, sensitivity analysis approach has been used to reduce computation time and effort. This technique has been applied to a 6 bus model and a 26 bus version of the Saskatchewan Power Corporation transmission system; and some of the more interesting results are presented.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.