Abstract
An approach for linearizing the nonlinearities of the high voltage direct current (HVDC) system for analyzing the system stability over wide range of operation is presented. The nonlinearities can be linearized with +or-5% error over a wide range of system operation. It is shown that the nonlinearities introduced by the converter, real power, and reactive power equations can be linearized over a wide range by using the integral square error (ISE) method. The results are compared with standard techniques called small signal analysis. It is shown that the stability margin of the system predicted by the new technique is relatively smaller than what is predicted by small signal analysis. The system stability boundaries are determined by the AC voltage and the reactive current control. These two control schemes may provide the same stability margin, provided appropriate controller gains are selected. The power factor control modeling is discussed.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.