Abstract
Maintaining the transient stability of the power system is very important for the stable and safe operating. This paper presents an analytical method of determining transient stability margin quantitatively using protection information for multi-generator system. First, the additional impedance of unbalanced fault is calculated by positive sequence equivalent rule. Based on the complementary cluster center of inertia-relative motion, the multi-machine system is equivalent to a one-machine infinity-bus system. Then, through the piecewise models of generator angles, the analytical expression of the equivalent fault clearing angle and the transient stability margin are obtained. Furthermore, the analytical stability margin is put forward to quantize the transient stability after fault occurred with the acquisition of the protection information, and the effects of fault location and fault clearing time on the stability margin under unbalanced faults are analyzed. Finally, four-machine two-area system is used as test system to investigate the effectiveness and accuracy of the proposed method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.