Abstract
The excitation transformer is a device that specifically provides three-phase AC excitation power for the generator excitation system. The excitation system converts the three-phase power to the generator rotor DC power through the thyristor to form the generator excitation magnetic field, which is adjusted by the excitation system thyristor trigger angle, to achieve the purpose of adjusting the motor terminal voltage and reactive power. This article analyzes an accident in which the excitation transformer high temperature signal is erroneously caused to cause the unit to trip. The unplanned shutdown accident is specifically analyzed from the aspects of on-site situation investigation, cause analysis, main problems exposed, treatment and preventive measures.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Earth and Environmental Science
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.