Abstract

In the presence of rate constraints in actuator, design of cascade controller based on the primary controller conditional integration can result into closed-loop system oscillations. Stability analysis, performed by the describing function technique and confirmed by simulation, demonstrates that the solution based on the Anti-Reset Windup Cascade Control System (ARW CCS) structure is successful. Design and tuning of the ARW CCS secondary controller is a standard ARW single-input single-output problem. In the present paper tuning is proposed for the ARW CCS primary controller. For the serial process modeling simple rules are derived and confirmed by experimental results, obtained on a drum type boiler of a 210MWe lignite coal fired unit. General design of the ARW CCS is based on the parallel process modeling and optimization of the primary controller. Optimization is performed in the frequency domain, under constraints on the maximum sensitivity, multiplicative uncertainty bound and sensitivity to measurement noise. Simulation and experimental results on a laboratory thermal plant demonstrate effectiveness of the proposed optimization.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.