Abstract
Regarding to dynamic nature of power system, short-circuit current also includes transient currents in addition to steady current. Transient components of fault currents may disturb the coordination between overcurrent (OC) and distance (Dis) relays because of the dependence of the operating time of inverse time overcurrent (OC) relays to the value of the short-circuit current. In this paper, a method for OC–OC and OC–Dis relay coordination, considering transient states of short-circuit currents, is presented. The dynamic model of the inverse time OC relay is used. A new formulation based on the dynamic model is presented to incorporate the pickup current (Ip) into the coordination algorithm, in addition to the time setting multiplier (TSM). To improve OC–OC and OC–Dis relay coordination, the selection of various curves types for OC relays is considered. Adapted particle swarm optimization (PSO) algorithm is used to obtain optimal results for the coordination of relays. The proposed OC–OC coordination and OC–Dis coordination methods are implemented on a radial and a meshed network, and the results are compared with the conventional method of coordination.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.