A fault location methodby dynamic system parameter estimation is presented for a double-end fed transmission line using a 1/4 to 1 cycle window of data at one local end only. The system differential equations are based on a lumped parameter line model, Thevenin equivalents for transients at both ends of the line and an unknown fault resistance. Simplification of the equations is obtained by using instantaneous symmetrical components. The estimation algorithm does not require filtering of d.c. offset and high-frequency components from the recorded signals and its accuracy is illustrated in digital simulation studies.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.