Abstract

This paper presents an accurate analytical method for calculating the leakage inductance of shell-type E-core transformers with rectangular windings. For this purpose, first, an expression for calculating the leakage inductance per unit length inside the core window considering the core walls as the flux-normal boundary condition is derived. Then, a new accurate method for determining the Mean Length of Turns (MLT) based on the total stored energy is presented. The MLT is needed for the leakage inductance calculation using 2-D methods. By dividing the MLT into three partial lengths and calculating the corresponding leakage inductances using three different core window arrangements, the effect of core structure on the total leakage inductance is considered. The method is verified by 3-D FEM simulations as well as the leakage inductance measurements on two different fabricated transformer prototypes. The superiority of the method is also confirmed by comparisons with the previous analytical approaches. The proposed method enables the leakage inductance calculation with an error less than 1%, compared to the 3-D FEM results. Using the presented method, the leakage inductance calculations can be performed rapidly and accurately in the design stage without the need for time-consuming 3-D FEM simulations.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call