Abstract
This article presents an alternative Newton-Raphson power flow method version. This method has been developed based on current injection equations formulated in polar coordinates. Likewise, the fast decoupled power flow, elaborated using current injection (BX version), is presented. These methods are tested considering electrical power systems composed of 57-, 118-, and 300-bus, as well as a realistic system of 787-bus. For the robustness analysis, simulations were performed considering different loading conditions and R/X ratios of the transmission line. Based on the simulations that were realized, there is evidence that the performance of the proposed current injection methods is similar to the power injection methods.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.