Abstract

This paper contributes the optimal allocation of DSTATCOM (distribution static compensator) and DG (distributed generation) in radial distribution systems using exhaustive search method (ESM) to reduce the power loss and improvement of the voltage profile. The certain range of active and reactive powers have been injected simultaneously at each node by incorporating the corresponding size of DSTATCOMs and DGs respectively into the radial distribution system (RDS). On the basis of best reduction in power loss, the Size of DSTATCOM and DG are determined. Forward-Backward sweep load flow algorithm was used for the load flow solutions. The results obtained by proposed approach shows the optimal allocation and sizing of DSTATCOM and DG in RDS efficaciously reduces the power loss and improves the voltage profile. The IEEE-30bus RDS was used as a test system.