Abstract
In this study, experiments are conducted on sine wave heat exchangers under wet condition, and the results are compared with those of herringbone wave heat exchangers having same wave height. Sine wave samples yield higher j and f factors than herringbone wave samples. The reason may be attributed to the reduced recirculation zone in the valleys of the sine wave channel. The effect of fin pitch on j and f factor is not pronounced both for sine and herringbone wave heat exchangers. The j factor decreases as number of tube row increases. However, the effect of number of tube row on f factor is dependent on the fin configuration. For herringbone wave samples, f factor decreases as the number of tube row increases. For sine wave samples, on the other hand, f factor is independent of the number of tube row. Ratios of j/f1/3 between sine wave and herringbone wave samples are between 0.95 and 1.0, which decrease with theincrease of fin pitch. A new correlation was developed based on the present data.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.