Air cooler is an important equipment of HTGR passive cavity cooling system. Structure optimization is necessary to improve the flow uniformity. In this work, the flow distribution characteristics are numerically investigated for four air coolers, including the Z-type, U-type, semi-Z-type and central-type arrangements. By comparison, the flow distribution of central-type arrangement is more uniform than that of other arrangements, with the non-uniformity coefficient reduction by 73%. Moreover, the phenomenon of static pressure recovery also appears in the distribution headers of semi-Z-type and central-type arrangements. Tube-side water flow in the central-type arrangement can be regarded as the parallel connection of two U-type arrangements. Central-type arrangement reports a symmetrical structure design, as the promising optimization for air cooler.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.