Abstract

The fungal contamination of air processed by an air-conditioning system can be quite high, depending on the technical features of different parts such as filtering and humidifying devices, as well as on their maintenance. The effect of filtration and humidification by sprayed water on the fungal air content was studied by analyzing the total culturable airborne fungi and four mold genera: Aspergillus, Beauveria, Cladosporium, and Penicillium. In four air-conditioning systems air samples were collected simultaneously on either side of the filters and humidifiers, using four single-stage viable particle samplers, on a malt agar chloramphenicol medium. High-efficiency filters (EU7) and lower efficiency filters (EU4)were compared, with actual efficiency calculated for every genus identified. The concentration levels measured below the high-efficiency filters were significantly lower than that measured above the filters. For the EU4 filters, the differences were not significant for Beauveria and Penicillium. F...

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call