Abstract
The effect of inclination angle on the heat transfer and pressure drop characteristics of brazed aluminum heat exchangers having louvered fins is experimentally investigated. Three samples having different fin pitches (1.25, 1,5 and 2.0 mm) were tested. Results show that heat transfer coefficients are not affected by the inclination angle. Friction factors, however, increase as the inclination angle increases, with negligible difference between the forward and the backward inclination. Both the heat transfer coefficient and the friction factor are the smallest at Fp = 1.5 mm, followed by 2.0 mm and 1.25 mm. Possible explanation is provided considering the louver layout. Comparison of the present data with existing correlations is also made.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.