Abstract

This paper analyses the possibility of using air curtains to prevent smoke flow from fire compartments. Full size experiments have been carried out and several relevant conditions to assess smoke-tightness have been tested. The smoke temperature during the tests was ranging from 182°C to 351°C, the angle measured between the curtain axis and the vertical plane was ranging from 18° and 26°, the nozzle thickness was ranging from 0.017 m to 0.045 m and the velocity at the nozzle was ranging from 8.3 m/s to 19.9 m/s. During the tests, the air curtain’s nozzle was positioned horizontally at the top of a permanent opening (door). With this configuration, we obtained an approximately vertical downward jet through the used opening. This paper includes the final results of the tests and develops an analytical tool for predicting the performance of air curtains. It was concluded that it is possible to achieve smoke-tightness, provided that the adequate plane jet parameters and the compartment’s smoke exhaust are correctly adjusted. According to this analysis, the smoke-tightness limit corresponds to equation $$ B = \Delta {\text{P}}_{\text{a}} /\Delta {\text{P}}_{\text{s}} = - 0.30 \,u_{a} /u_{a\_min} + 1.25 $$ (with $$ 1.30 \le u_{a} /u_{a\_min} \le 1.67 $$ ).

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.