Abstract
A failure of a 7 1/2-year-old commercial rooftop air conditioning system was investigated. The systematic failure analysis procedure and eventual discovery of a leak in a pure copper condenser coil are discussed. Severe denting of several tubes, including the tube that leaked, was discovered in the area of the steel tube sheet. A metallurgical examination, including scanning electron microscopy, revealed intergranular cracking, a process that is common among some copper alloys suffering from stress-corrosion cracking but is rarely observed in pure copper. Research of available literature is presented, and the conditions under which pure copper may exhibit intergranular cracking are discussed. Also presented are vibration measurements of the air conditioner taken during operation, which rule out operating loads as the cause of the tube denting and eventual cracking. The cause of the denting remains unknown. However, the denting probably occurred during manufacturing, and the high stresses associated with the dents, in the presence of corrosion, resulted in intergranular cracking and eventual leaking.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.