Abstract

With the present state of the direct current (DC) distribution market, securing the safety of the DC distribution system is emerging as a major issue. Like AC distribution systems, DC switches and circuit breakers are one of the main means to ensure safety. However, in the DC system, since there is no current zero point in the load current, the phenomenon occurring when the circuit is cut off is different from that of the AC system, so technical research is required to cope with this. In this study, the aging characteristics of the contact electrode of a 400 V class low voltage DC (LVDC) switch is studied for the development of wall-mount switches or circuit breakers for residential houses. As an arc extinguishing method to break DC load current, a prototype experimental circuit breaker that uses a magnetic extinguishing method that is effective for blocking low voltage low power DC is invented, and an automated experiment system is established. The DC switch test repeats the operation of turning it on and off 13,000 times, and continuously evaluates the performance of the electric contacts by calculating the voltage drop between the electrode contacts and the corresponding Ohmic resistance value when conducting every 500 times. This paper tests six contact materials to compare the aging characteristics of them by evaluating contact resistance during the test period. AW18-Cu composite material showed the most stable and excellent contact performance for LVDC switches during the entire test operation period.

Highlights

  • The necessity of direct current (DC) distribution has emerged in accordance with the demand for renewable power generation, and the increased DC load and energy efficiency requirement.Direct current distribution technology is already applied in the various fields of photovoltaic power generation [1], wind generation [2], data centers [3,4], electric vehicles [5], etc

  • We study the aging characteristics of the contact points of a 400 V class residential low voltage DC (LVDC) switch

  • This paper evaluated six kinds of contact materials for the application of low-voltage

Read more

Summary

Introduction

The necessity of DC distribution has emerged in accordance with the demand for renewable power generation, and the increased DC load and energy efficiency requirement. IEC 60898-3 regulates that the circuit breaker is submitted to 1000 operating cycles with rated current and to 3000 operating cycles without load [19] This means that the voltage drop between electrode contacts should not be greater than mV after 1000 operating cycles with the load current not more than 10 A. As an arc extinguishing method for breaking DC load current, a prototype experimental circuit breaker with a magnetic extinguishing method that is effective for breaking of low power LVDC load was invented, and an automated test system was established [20]. The DC switch test repeats the operation of turning on for about 1.5 s and turning off for 2 s, 13,000 times, and continuously evaluates the performance of the electrode by calculating the voltage drop between the electric contacts and the corresponding Ohmic resistance value when conducting, every 500 times

Experimental Condition
Experimental Results
Aging Characteristics of Electrode Contacts
Conclusions
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.