Abstract
To explore the aging assessment method of the oil–paper insulation in power transformers, the polarization and depolarization current (PDC) characteristics of oil–paper composite insulation samples are investigated under high applied voltage. Based on the asymmetry of polarization absorption current and depolarization current and the polarity effect of insulation pressboard, the repeated polarization current test method is proposed. A novel aging characteristic parameter, which is the ratio of the normalized charge for the first polarization and the normalized charge for the second polarization, is extracted. The difference between the decay rates of the first polarization current and the second polarization current increases at first and then decreases with the polarization time, and decreases with increasing aging degree of the pressboard. The more serious the insulation aging is, the smaller the variation range of aging characteristic parameter with polarization time is, and the closer the value is to 1. With decrease in the DP, the maximum of aging characteristic parameter changes in a decreasing trend. The aging condition of the oil–paper composite insulation can be assessed by the repeated polarization current method and the relationship between the aging characteristic parameter and the polarization time.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.