Abstract

The absorption process has been confirmed as the most important process in absorption refrigeration machines in terms of improving their total efficiency. One of the key research directions is the selection of absorber structure which is expected to be fabricated in Vietnam without demand of new infrastructure investment. In this study, a local model of the coupled heat and mass transfer during absorption process of NH3 vapor by a NH3-H2O diluted solution flowing over horizontal round tubes of an absorber was made. The heat transfer coefficient obtained from the coupled heat and mass transfer mathematic model. This heat transfer coefficient is used to calculate the variation of the simulated value of heat load. The correlations which give the heat transfer coefficient and mass transfer coefficient in the absorption process in range of solution concentration ω = 28% ÷ 31%, solution mass flow rate per unit tube length Γ = 0.001 ÷ 0.03 kgm-1s-1, coolant temperature twater = 28 oC ÷ 38 oC are set as two functions. The practical decrease of wetted ratio analyses were taken into account when the solution flow from the top to the bottom of the parallel tube bundle. The deviation of theoretical heat load and experimental heat load is about 12.3%. Based on these simulations, the theoretical studies were done for absorption refrigeration system in order to narrow the working area where the experiments later focused on. The results of this study will be the basis for subsequent application research of falling film absorbers.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call