Abstract
An analytical investigation has been performed to study the possibility of application of solar cooling for the climatic condition of Tokyo, Japan. Silica gel–water adsorption cooling system has been taken into consideration for the present study and lumped parameter model is used to investigate the performance of the system. Based on the solar radiation data it is found that at least 15 collector (each of 2.415m2) is required to achieve the required heat source temperature (around 85°C) to run the cooling unit. It is also observed that the solar powered adsorption cooling unit provides cooling capacity around 10kW at noon with base run conditions, while the system provides solar COP around 0.3, however, the solar collector size can be reduced by optimizing the cycle time.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.