Abstract

In this paper, an analytical method of computing the admittance matrix is introduced that facilitates the stability analysis of DC micro-grid systems, in presence of constant power loads (CPLs). Due to their nonlinear behaviour, CPLs can yield instability in DC micro-grids; an effect referred to as ‘negative impedance instability’. The proposed method is particularly useful when a typical controller (droop control, voltage regulation) is designed to control the DC bus voltage of the micro-grid, as it allows the factorisation of the admittance matrix separating singular matrices. In doing so, the closed-loop stability proof can be more easily approached by isolating the singularities and, then employing straightforward linear algebra tools to arrive at the stability conditions. In order to validate the proposed approach, compute the admittance matrix and test the stability conditions, a DC micro-grid with n DC/DC power converters connected to a CPL is considered. Simulation results are also displayed to demonstrate the desired operation of the DC micro-grid control and design framework.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.