Abstract
Nowadays, composite insulators are widely utilized in power systems because of their undeniably important advantages over non-ceramic insulators. Effective use of these insulators, however, entails adjusting the voltage and e-field distribution along them which are inherently much more non-linear comparing to non-ceramic insulators. In this paper, corona ring design for a 400kV composite insulator is investigated aiming at e-field and voltage regulation along the insulator. The analysis is based upon Finite Element Method (FEM) and the results obtained through the simulations. The effects of the corona ring's design parameters on e-field and voltage control are studied. Appropriate dimensions and position of the rings are then determined for effective adjustment of the voltage as well as e-field distribution. Moreover, the simulation is also conducted for double corona rings at the energized end and the results are compared to those in the case of single ring.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.