Abstract

This paper presents a new synchronization scheme for detecting multiple positive-/negative-sequence frequency harmonics in three-phase systems for grid-connected power converters. The proposed technique is called MAVF-FLL because it is based on the use of multiple adaptive vectorial filters (AVFs) working together inside a harmonic decoupling network, resting on a frequency-locked loop (FLL) which makes the system frequency adaptive. The method uses the vectorial properties of the three-phase input signal in the αβ reference frame in order to obtain the different harmonic components. The MAVF-FLL is fully designed and analyzed, addressing the tuning procedure in order to obtain the desired and predefined performance. The proposed algorithm is evaluated by both simulation and experimental results, demonstrating its ability to perform as required for detecting different harmonic components under a highly unbalanced and distorted input grid voltage.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call