Abstract
Fast and accurate methods of fault detection and isolation are a pre-emptive measure in multiterminal dc (MTdc) systems. Zonal isolation of faults is necessary to prevent any misopertation of the dc breakers that can lead to a shutdown of the network. Existing techniques require fast-communication or data synchronization methods have their own disadvantages. This article proposes a method for efficient fault zone isolation without the need of a communication link that prevents any misoperation of the dc breakers in a radial MTdc. This method provides individual local measurement-based control to the hybrid dc circuit breakers (dcCB). Faults created outside the zone of protection for a breaker create a change in the rate of change of current or voltage leading to misoperation. To avoid detection using a fixed threshold, an adaptive threshold based approach is suggested that updates the threshold based on the present operating status. Sensitivity analysis by varying the current limiting inductance and fault location is performed. A three terminal radial model of an MTdc is used for zonal isolation using power system computer aided design/electromagnetic transients including dc.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.