Abstract

This paper proposes sensorless control strategies for an offshore wind farm (OWF) and voltage source converter high voltage direct current (VSC-HVdc) stations. The extended Kalman filter provides an estimation of the speeds and rotor positions of permanent magnet synchronous generators (PMSGs) of OWF, the dc voltage at dc-bus and the dc voltages of the both VSC-HVdc stations. The OWF, composed of 150 variable speed wind turbines based on PMSGs, is considered in this paper, where each generator is connected in series by its own ac-dc converter to dc-bus. Only one dc-ac inverter converts the dc-bus voltage to a proper ac voltage of wind farm ac-bus. The HVdc transmission system based on a three-level neutral point clamped VSC is used for the interconnection between the OWF and the onshore grid via two dc cables. Detailed modeling and control strategies are developed for each individual component of the system. Simulation results show the effectiveness of the proposed method to manage the desired HVdc system operation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.