Abstract

In this paper we propose an approach based on an Online Feedback Optimization (OFO) controller with grid input–output sensitivity estimation for real-time grid operation, e.g., at subsecond time scales. The OFO controller uses grid measurements as feedback to update the value of the controllable elements in the grid, and track the solution of a time-varying AC Optimal Power Flow (AC-OPF). Instead of relying on a full grid model, e.g., grid admittance matrix, OFO only requires the steady-state sensitivity relating a change in the controllable inputs, e.g., power injections set-points, to a change in the measured outputs, e.g., voltage magnitudes. Since an inaccurate sensitivity may lead to a model-mismatch and jeopardize the performance, we propose a recursive least-squares estimation that enables OFO to learn the sensitivity from measurements during real-time operation, turning OFO into a model-free approach. We analytically certify the convergence of the proposed OFO with sensitivity estimation, and validate its performance on a simulation using the IEEE 123-bus test feeder, and comparing it against a state-of-the-art OFO with constant sensitivity.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call