The dynamic behaviour of microgrid system under faulty conditions makes adaptive protection a general necessity for reliable microgrid operation. In design of adaptive protection, the grid-connected and islanded modes have immense importance including grid-connected mode without distributed generators (DGs) in microgrid. In this study, a new adaptive protection scheme is proposed based on the above-mentioned modes of microgrid operation. The proposed method considers nature of DGs connected, fault location detection and fault nature identification based on quadrature and zero sequence components of fault current considering impact of X/R ratio of DGs. The proposed methodologies for adaptive protection schemes are verified in Matlab-Simulink environment and the results are found to be satisfactory while various faults are simulated at different nodes of the microgrid model. At the time of verification of effectiveness of the proposed methodologies, the time derivative of quadrature and zero-axis components of fault current are considered sufficient to instantaneously detect the fault location and fault nature in microgrid system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.