Abstract
The operational performance of conventional overcurrent protection relay coordination connected to a distribution network is adversely affected by the penetration of distributed generators (DG) at different buses in the network. To address this problem, this paper proposes a novel adaptive protection coordination scheme using a radial basis function neural network (RBFNN), which automatically adjusts the overcurrent relay settings, i.e., time setting multiplier (TSM) and plug setting multiplier (PSM) based on the penetration of DGs. Short circuit currents and voltages measured at different buses are acquired using the remote terminal units (RTU) connected to different buses within the terminal network. Communication between the various remotes and local end station RTUs is through hybrid communication systems of fiber optic and power line communication system modules. The new adaptive overcurrent protection scheme is applied to the IEEE 33-bus distribution network with and without DGs, for single and multi-DG penetration using both the ETAP and MATLAB software. The simulation results show the proposed scheme significantly improves the protection coordination.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.