Abstract

The adaptive fuzzy faults tolerant control problem is investigated for a single machine bus system with static var compensator (SVC). This design does not require that speed of the generator rotor and susceptance of the overall system are measured, and also does not require that the parameters of the controlled system are known accurately. The considered faults are modeled as both loss of effectiveness and lock-in-place. A fuzzy state observer is designed to estimate the speed of the generator rotor and susceptance, by combining the adaptive backstepping technique with a dynamic surface control (DSC) approach, a novel adaptive fuzzy output-feedback faults tolerant control approach is developed. It is proved that the proposed control approach can guarantee that all the signals in the closed-loop system are semiglobally uniformly ultimately bounded (SGUUB), and the angle of the generator rotor follows a desired value. Simulation results are presented to show the effectiveness of the approach.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.